NEUTRAL GROUNDING REACTORS
|
Neutral Grounding Reactors are single phase reactors generally connected between ground and neutral of transformers, generators. Neutral Grounding Reactors are used in order to limit maximum fault current to a value which will not damage the equipment in the power system, yet allow sufficient flow of fault current to operate protective relays to clear the fault.
COMMON REASONS for USING NEUTRAL GROUNDING REACTORS
- Reducing single phase earth fault currents which occur in M.V. electrical networks to prevent damages on transformers and generators,
- Reducing temporary over voltages occurred by braking instantaneous fault current,
- Providing long-life for switchgear,
- Reducing step voltages to a harmless level for personnel.
|
|
ADVANTAGES
Perfect mechanical strength to withstand high short-circuit forces.
Limited temperature rise enables longer lifetime.
Special surface protection against UV and pollution class IV areas.
Maintenance-free design
|
|
 |
|
|
STANDARD
EN 60289 or depending on customer requirements. |
| |
FEATURES
Air core
Dry type
Side by side, delta or vertical arrangement depending on space availability
Outdoor and indoor
Enclosures are available on demand
Elevated support stands are available
Suitable corona rings are provided with reactors over 170 kV in order to eliminate visible corona
Aluminum or copper winding
RAL 7032 or other colors
- 40 ºC / + 55 ºC ambient temperature range
F class (155 ºC) protection degree or customer specific design
Taps are available
Fiberglass resin spacers are used in order to provide ease of cooling
AN (air-natural) cooling method |
| |
INSULATION
. F class (155 ºC) film insulation or epoxy resin reinforced fiberglass.
. Epoxy based paint & insulating varnish.
INSTALLATION
The height and the diameter of the reactor can be adjusted to customer specific needs in order to meet unusual space requirements |
Complete installation guidelines are provided with the reactors in order to meet required magnetic clearances on close metallic structures. Each reactor is supplied with an INSTALLATION GUIDELINES that specifies minimum magnetic clearances for the reactor.
SUPPORT STANDS
Aluminum, hot dip galvanized steel or concrete support stands are designed for specific applications.
|
|
 |
| |
LOSSES
All Hilkar Electric reactors are computer designed in order to minimize investment and operating losses.
TESTS
All the routine tests are performed in accordance with EN 60289 or other standards depending on customer request. Type test reports are available on request. All the test reports are submitted to customer.
Basic testing program includes some or all of the following tests:
Routine Tests (Inductance, Resistance, One Minute AC Insulation Voltage Withstand Test and Impulse Voltage Withstand Test)
Short Circuit Withstand Test
Temperature Rise Test
Sound Level Test
Seismic Test
QUALITY ASSURANCE
Hilkar maintains a complete quality assurance program including ISO 9001 and other major industry standards in it's manufacturing plant.
TECHNICAL SUPPORT
Hilkar provides complete technical assistance to contractors and end customers for applications, design, calculations and field installation. All Hilkar reactors are custom designed for different applications by considering the voltage, current, inductance, size, loss characteristics that are required to provide the most efficient design at the most economical prices.
|
| |
| |
| |